For pressurisation, deaeration and topping up in sealed heating installations (acc. to EN12828) and chilled water (cooling) installations.
Sinum pump units are used for storage of expansion water, deaeration and topping up your installation automatically as an integrated controlled unit carried out with state of the art micro-electronics. The Sinum balanced pressure expansion equipment is sized according to the total system volume and the boiler or chiller load. The Sinum vessel is 80% efficient irrespective of the static height of the system. It is the ideal solution for large installations or high installations where standard diaphragm expansion equipment is limited.
Special features/product advantages
- Easy installation thanks to intuitive menu navigation in the HMI, large display and self-learning microprocessor.
- Different operating modes guarantee continuous degassing.
- Advanced technology ensures low power consumption, long service life and easy maintenance.
- Improved convenience through volumetric controls and automatic topping-up during the heating and cooling cycles.
- Modular design offers a high level of installation flexibility.
- Optional: Integration in existing building management systems through digital and analogue outputs.
Dimension, weight
Width with packaging
750 mm
Net weight, approx.
105 kg
Height
974 mm
Height with packaging
1435 mm
Gross weight, approx.
135 kg
Width
605 mm
Length
540 mm
Length with packaging
600 mm
Product data
Date of sales availability
2018-07-01
Minimum order quantity
1
Article number
2198864
Product description
Sinum single-pump unit M130 400V
EAN number
4048482837819
Colour
White
Brand
Wilo
Technical data
Min. fluid temperature
3 °C
Min. boiler output
3300 kW
Min. ambient temperature
3 °C
Max. fluid temperature
70 °C
Installation
Vertical
Max. operating pressure
16 bar
Max. ambient temperature
50 °C
Digital control unit
Yes
Max. boiler output
5300 kW
Max. refill pressure
6 bar
Connectable
Yes
Min. refill pressure
4 bar
Min. working pressure
8
Max. working pressure
14.4
Maximum allowed limit of glycol in %
50 %
Max. feed temperature in the system
105 °C
Packaging
Pieces per pallet
1
Packaging type
Euro pallet
Packaging property
Transport packaging
Number per layer
1
Motor data
Mains frequency
50 Hz
Rated voltage
400 V
Protection class
IP54
Voltage tolerance
±10 %
Rated current
7.8 A
Sound-pressure level
55 dB
Phases
3
Installation dimensions
Connection outlet
G 1½
Connection inlet
G 1½
Артикул | Название | Цена | ||
---|---|---|---|---|
2198858 | Sinum single-pump unit M2 230V | Цена по запросу | ||
2198859 | Sinum single-pump unit M10 230V | Цена по запросу | ||
2198860 | Sinum single-pump unit M20 400V | Цена по запросу | ||
2198861 | Sinum single-pump unit M60 400V | Цена по запросу | ||
2198862 | Sinum single-pump unit M80 400V | Цена по запросу | ||
2198863 | Sinum single-pump unit M100 400V | Цена по запросу | ||
2198864 | Sinum single-pump unit M130 400V | Цена по запросу |