Pressure boosting system as a fully automatic compact unit for firefighting purposes in accordance with EN 12845.

Consisting of a pump with horizontal base frame — EN 733 — with spacer coupling (up to 17,7kW) or cardanic joint (above 17,7kW), diesel motor and one switch cabinet, fixed to a robust support structure.

Model D for the diesel motor, equipped with firefighting dedicated controller, solid construction made of special profiled parts with cut-outs for forklift trucks and hooks to ensure trouble-free, safe transportation.

A circuit with dual pressure switch, pressure gauge, non-return valve, valve (secured from use by unauthorised personnel) for the main pump for automatic start. Equipped with a diaphragm installed directly on the main pump housing as standard, to prevent overheating in the event of zero flow.

Separated fuel tank with level sensor and adequate volume to allow 6 hours operating autonomy and 2 batteries on the base plate and battery chargers in the control box.

Control D switchgear for fire extinguishing systems according to EN 12845.

Switchgear integrated in a sheet metal enclosure in accordance with protection class IP54. Very high control quality and very simple operation due to the firefighting dedicated controller, with multi-languages screen, easy navigation with simple menu and push button plus immediate operation status with symbols. Communication-ready controller for supervising systems operations.

The system has been mounted on the base frame with wires and pipes are ready for connection.

Inlet pressure:

The maximum inlet pressure must be taken into account when designing the system configuration (see Technical data). The maximum permissible inlet pressure is calculated from the maximum operating pressure of the system minus the maximum delivery head of the pump at Q = 0. For sprinkler systems in accordance with EN 12845, the water pressure should not exceed 12 bar. In sprinkler systems with a pronounced slope, in which the difference in height between the highest and lowest sprinkler is more than 45 m, the water pressure can be higher than 12 bar at the pump outlet or in the piping, provided that all of the system components are designed for this pressure level.

Installation of the pressure boosting pump under suction conditions.

For the main pump, it is necessary to install a supply tank with connection to the discharge pipe above the pump.

Volume flow

Up to 320 m³/h (89 l/s) system configuration for the main pump.

Switchgear/control device for fire water supply systems

Wilo-Control D (main pump with diesel motor)

Hardware:

Fully electronic central control unit, built in painted steel case, with protection class IP 54, control and display devices on the front door.

Features and functions:

The controller design is suitable for the performance of each motor-pump combination. The device comprises the following components:

Main switch: For switching the switchgear On/Off. (Unauthorized action in case of fire).

Display: Back lighted graphic LCD display, built into the switch cabinet door for operating and display purposes. Displays the operating data and the receptive current operating statuses of pump and the controller. The menu selection as well as the parameter input are done by push buttons on the front door.

Microprocessor: Integrated PLC logic with thresholds, counters, alarms, status; 12 VAC auxiliary power supply; advanced I/O wired functions. The respective programming configuration is strictly dependent on system and sprinkler installation.

Indicators: Long-life indicator lights to show, power supply status, pump running, motor status, pressure switch on, battery status, battery selection, automatic mode excluded, manual reset, alarm stop.

Buttons: Push button to manage manual stop, manual start battery A, manual start battery B, manual test mode, alarm reset and menu selection.

Fuse protection: Protection fuses for auxiliary contacts and battery charger.

Motor startup: Automatically via two alternating batteries or directly on each battery with start button on the front panel.

Motor protection: Monitoring of typical operating parameters of diesel engine (Temperature, oil pressure, fuel level, and so on) without stop.

Priming tank monitoring: By float switch to keep the water level at minimum 2/3 of the priming tank.

Power monitoring: Speed monitoring of diesel engine.

Battery monitoring: Monitoring of charge voltage, charge current and failure of charger.

Monitoring and controlling: Power supply, engine cooling temperature and oil pressure, analog sensors pressure and temperature, fuel level, batteries voltage, working hours of the engine, pump status, alarm status, pump statistics and starts, Jockey pump starts (if available), maintenance program, pump room temperature and ventilation.

Fault message and acknowledgment: All alarm messages are displayed via LEDs or the graphic LCD. The LEDs color and alarm code must be acknowledged.

Software:

  • Factory-programmed for fully automatic operation
  • Information regarding motor speed, charging voltage and charging current.
  • Menu navigation with text on display

Communication:

  • Isolated RS485 communication interface built in with Modbus RTU protocol.
  • Front optical programming interface, high speed, USB and Wi-Fi compatible, wireless setup with NFC technology.

Conforms to the following standards:

  • Fixed automatic Sprinkler Systems — (EN 12845), part for pumps with diesel motor
  • Electrical equipment of machines (EN 60204-1)
  • Low-voltage switchgear and control gear assemblies (EN 61439-1 and EN 61439-2)
  • Electromagnetic compatibility (EMC) — Immunity for industrial environments (EN 61000-6-2)
  • Electromagnetic compatibility (EMC) — Emission standard for residential, commercial and light-industrial environments (EN 61000-6-3)

Function description:

Wilo D control devices can be used to control pumps with a diesel motor, sensors for pump management and the level of information. The microprocessor-controlled switchgear is used to control and regulate all required functions of a pressure boosting system according to EN 12845, for test purposes or actual sprinkler events.

The operating logic for the fire extinguishing unit is based on the cascade calibration of the pressure switches for starting the pump.

If a large amount of water is requested due to the opening of one or more circuits or due to a defective sprinkler, the pressure in the system decreases. As a result, the main pump is started using switchgear. If the diesel main pump does not start in systems with multiple pumps (for example due to problems with the power supply), a pressure drop will activate the pressure switch of the standby pump, which starts this pump. In some cases, two or more diesel pumps can be used.

As soon as the sprinkler circuit or gate valve, via which the sprinkler heads are supplied, is closed, pressure is built up in the system. The stop buttons on the front door must then be pressed to stop the pump.

Dimension, weight
Width with packaging
1948 mm
Net weight, approx.
404 kg
Height with packaging
1602 mm
Width
1748 mm
Length with packaging
768 mm
Height
1472 mm
Length
568 mm
Gross weight, approx.
455 kg
Materials
Pipework material
Steel 
Shaft
Stainless steel 
Gasket material
EPDM 
Impeller
Bronze 
Pump housing
Grey cast iron 
Hydraulic data
Max. fluid temperature
25 °C
Maximum operating pressure
16 bar
Max. ambient temperature
40 °C
Min. ambient temperature
4 °C
Min. fluid temperature
4 °C
Number of pumps
Diesel engine
Rated power
12500 W
Cooling method
Air 
Cylinder capacity
0.954 l 
Rated speed
2900 1/min
Cylinder number
Air volume flow cooling
792 m³/h
Product data
Colour
Red/black/silver 
Date of sales availability
2020-09-01 
Article number
4240831 
Brand
Wilo 
Minimum order quantity
Product description
SiFire-FIRST-50/200-192-12,9D 
EAN number
4062679049359 
Packaging
Packaging type
One-way pallet 
Packaging property
Sales packaging 
Number per layer
Pieces per pallet
Installation dimensions
Pipe connection on the suction side
DN 65 
Pipe connection on the discharge side
DN 65 
Артикул Название Цена
4240913 SiFire-FIRST-100/200-222-66DJ Цена по запросу
4240890 SiFire-FIRST-50/250-242-26,5DJ Цена по запросу
4240891 SiFire-FIRST-50/250-249-31,5DJ Цена по запросу
4240892 SiFire-FIRST-50/250-258-37DJ Цена по запросу
4240894 SiFire-FIRST-65/200-178-17,7DJ Цена по запросу
4240895 SiFire-FIRST-65/200-185-17,7DJ Цена по запросу
4240896 SiFire-FIRST-65/200-195-26,5DJ Цена по запросу
4240897 SiFire-FIRST-65/200-207-26,5DJ Цена по запросу
4240898 SiFire-FIRST-65/200-214-31,5DJ Цена по запросу
4240899 SiFire-FIRST-65/200-226-37DJ Цена по запросу
4240900 SiFire-FIRST-65/250-226-31,5DJ Цена по запросу
4240901 SiFire-FIRST-65/250-248-37DJ Цена по запросу
4240903 SiFire-FIRST-65/250-264-47,7DJ Цена по запросу
4240902 SiFire-FIRST-65/250-258-47,7DJ Цена по запросу
4240912 SiFire-FIRST-100/200-212-47,7DJ Цена по запросу
4240910 SiFire-FIRST-80/250-235-66DJ Цена по запросу
4240909 SiFire-FIRST-80/200-228-47,7DJ Цена по запросу
4240908 SiFire-FIRST-80/200-224-47,7DJ Цена по запросу
4240906 SiFire-FIRST-80/200-201-31,5DJ Цена по запросу
4240907 SiFire-FIRST-80/200-210-37DJ Цена по запросу
4240904 SiFire-FIRST-80/200-185-26,5DJ Цена по запросу
4240905 SiFire-FIRST-80/200-195-26,5DJ Цена по запросу
4240854 SiFire-FIRST-80/200-210-37D Цена по запросу
4240853 SiFire-FIRST-80/200-201-31,5D Цена по запросу
4240855 SiFire-FIRST-80/200-224-47,7D Цена по запросу

Вы недавно смотрели